How the IV sweep works

The measurement principle behind every Voc, Isc and Vop/Iop reading this dashboard shows for PV1–PV6: the shared circuit, the relay sequence, and how a wireless link between two boards turns a simple on/off relay into a curve tracer.

Hardware
ECM50 controller + LILYGO T-Relay-S3 × 3
Panels
PV1–PV6
Scope
measurement principle, not a source listing
Updated
2026-10-23 (ECM50 v2.7.0, T-Relay v1.0.4)

1System overview

Four physical pieces, one of which is shared by all six panels. That shared piece shapes everything else here.

Each of the six panels connects to the T-Relay boards: three relay boards, two panels each. The T-Relay's only job is to switch relays on command and report back when it has. All the electrical measurement happens through a single shared energy meter, read over RS485/Modbus by the ECM50 controller. A per-panel select relay decides which one panel, out of six, is patched through to that meter.

Panels PV1–PV6T-Relay-S3 × 3relay multiplexerShared energy meterRS485 / ModbusECM50 controllerSprout platformMQTTrelay switchingselect: 1 of 6 on the meterESP-NOW (wireless)RS485 ModbusWiFi / MQTT
Fig. 1Only one panel is ever connected to the meter at a time, which is why this is a sweep: it cycles through all six rather than measuring them in parallel.

The T-Relay sits close to the panels to keep relay wiring short; the ECM50 sits with the meter and the rest of the sensor bus. The two talk over ESP-NOW, a direct wireless link that needs no WiFi router or internet connection (§5).

2The measurement cycle

Each panel is driven through four relay states in order. Each state is a deliberate equivalent circuit.

Phase 1

Voc

S, I on · L off

No load connected. Terminal voltage settles at the open-circuit voltage; current is ~0.

holds ~1.5 s

Phase 2

Isc

S, I, L on

A dead short closes across the terminals. Voltage collapses toward 0; current rises to the short-circuit current.

holds ~1.5 s

Phase 3

Load (Vop/Iop)

S, L on · I off

The short is removed; current flows through a fixed load resistor. The panel settles at the point it would deliver into that load.

holds ~1.5 s

Phase 4

Break

S, L off

Panel released from the bus before the next one's turn: break-before-make, so two panels are never connected at once.

holds ~0.1 s

Why four phases, not one reading

A single resistor only ever shows one point on a panel's curve. Visiting open-circuit and short-circuit as well brackets the whole curve, and the firmware also captures what happens between those two states (§3).

Each held phase lasts about 1.5 s and the break about 0.1 s, so one panel takes roughly 4.6 s and a full six-panel sweep about 27.6 s.

3Where the curve comes from

There is no continuously variable electronic load anywhere in this system.

Relay contacts don't switch instantly. Between the Voc phase ending and the Isc phase beginning there is a real electromechanical transition, measured on the bench at roughly 120–150 ms. During that window the panel's terminal voltage and current pass through every intermediate value between Voc and Isc, as a slow sweep would.

The firmware samples the meter as fast as the RS485 bus allows during that window, instead of at its normal background rate. Those samples, typically 10–15 per panel, are the IV curve. The relay's own switching transient does the sweeping; the firmware only has to listen fast enough to catch it.

RegimeSample spacingWhy
Steady state (Voc / Isc / Load plateaus)every 50 msOnly a stable average is needed; no benefit to sampling faster.
Voc → Isc transition (the curve)~1 mains cycle (20 ms)The only window where the operating point is moving; resolution matters here.

What the curve registers hold (since ECM50 v2.6.0)

The curve points published per panel are now the first 18 samples of the Isc phase, sent unfiltered. Before 2026-10-22 they were the Voc → Isc transition samples, so curves from before and after that date are not directly comparable.

The same window yields Vmp/Imp/Pmax: the firmware scans every transition sample for the highest V×I product. It is a genuine point on the measured curve, not an estimate.

4From samples to numbers

Values published per panel per sweep, and where each comes from.

ValueSource phaseDerivation
VocVoc plateauAverage of the stable run of samples
IscIsc plateauAverage of the stable run of samples
Vmp/Imp / PmaxVoc → Isc transitionHighest V×I sample in the transition
Vop/Iop / PopLoad plateauAverage of the stable run of samples

A plateau isn't accepted as-is: the firmware finds the longest contiguous stretch where the reading holds within a tight tolerance, discarding the settling edges. A plateau that never settles (too short, too noisy) is rejected rather than averaged into a misleading number.

Fallback when the main analysis rejects a panel (since ECM50 v2.6.0)

If the main analysis rejects a panel, a simpler fallback works out Voc, Isc, Vop/Iop, Vmp/Imp and Pmax from the samples T-Relay tagged with each phase, and publishes them as valid. That's why all-zero sweeps became much rarer from 2026-10-22. Which sweeps used the fallback is recorded only in the controller's SD-card log, not in the published data. In v2.7.0, two checks that were rejecting the small lab cells were also loosened.

Vop/Iop vs Vmp/Imp: not the same point

Vmp/Imp is where the panel could deliver the most power, found on the measured curve. Vop/Iop is where it actually operates on a fixed load resistor. A fixed resistor can't track the maximum power point as conditions change, so the two are expected to diverge; the gap is itself useful (the MPP ratio on each panel page).

Voltage (V)Current (mA)IscVocVmp, Imp (max power)Vop, Iop (fixed load)
Fig. 2Illustrative curve shape. Isc and Voc bracket it; Vmp/Imp is the best point on the measured curve; Vop/Iop is where the fixed load sits, usually a little short of the knee.

6Sweep orchestration

ECM50's side of a sweep is a small state machine, so a stalled or dropped sweep can never lock the RS485 bus.

IV_IDLEIV_AWAITING_ACKIV_CAPTURINGIV_PROCESSINGtrigger(schedule / manual / irradiance)ACK receivedSWEEP_DONEor 45 s timeoutno ACK after 5 attemptsresults published
Fig. 4A timed-out capture is still processed on whatever samples arrived, so a dropped final message doesn't discard an otherwise complete sweep.

Automatic sweeps fire three ways: on a 15-minute clock-aligned schedule, when irradiance crosses a bright-sun threshold, or manually from the console (SWEEPNOW). Automatic triggers are suppressed after dark, since V and I read ~0 with no light and every sweep wears the relays for no usable data.

Night gate

Checked first against the weather station's lux reading (below a low threshold means too dark). If that sensor isn't answering, it falls back to a fixed clock window, currently 19:00–06:30. Manual sweeps always bypass the gate.

7Keeping Vop/Iop fresh between full sweeps

The full four-phase cycle is slow and wears six sets of relays. Most of the time only Vop/Iop needs refreshing.

A quick load poll skips straight to the Load relay state on each panel in turn (the phase 3 circuit, set directly), takes one reading, and moves on. It reuses the same messages and the same ECM50 state machine as a full sweep, so the two can never run at once or collide on the shared bus.

Full sweepQuick load poll
Phases visitedVoc → Isc → Load → BreakLoad → Break
Values refreshedVoc, Isc, Vmp/Imp/Pmax, Vop/Iop/Pop, curveVop/Iop/Pop
Default scheduleevery 15 minevery 5 min
Relay cycles per run (6 panels)6 × full sequence6 × one step
ECM50 / T-Relay firmware: measurement-principle summary, not a full implementation reference.